This product is designed with artistic outline, easy wire connection and simple installation, simple maintenance, working in a relatively harsh environment and maintaining in a long-term stability. This product is applied to AC / DC front end of power distribution equipment, it can effectively prevent over voltage and over current which are induced by lightning or industrial noise and other factors, and other transient surge voltage on the system or equipment or cause permanent damage or momentarily interruption and other hazards.
◆ The product apply to lightning protection zone: LPZ1 area or LPZ2 area at the junction with the LPZ3 power lines of the lightning surge protection.
◆ With advantage of stable performance, small residual voltage, fast response time and long lifetime.
◆ Core components are selected international brands, they have high reliability.
◆ It is designed with multi-stage protection circuit to make sure the protected equipment more safer.
◆ With temperature control breaker to effectively prevent fires.
◆ Apply to 220 V power supply lightning surge protection of equipment, such as: Distribution panel, power supply equipment, distribution box, electronic information system ark (such as the fire engine room line), and it is applicable to lightning protection of background music acoustics wire.
(2) Technology parameters:
TYPE:
|
JM-D220
|
Protection Class:
|
D
|
Operating Voltage (Un):
|
220V
|
Nominal Discharge Current (8/20μs) (In):
|
5KA
|
Voltage Protection Level( Up):
|
≤1.0KV
|
Response Time:
|
< 25ns
|
Leakage current:
|
≤20μA
|
Working Environment:
|
Temperature -40°C~+70°C;Relative humidity<90%
|
Protection Mode:
|
L/+~PE,N/-~PE
|
Material of Outer Shell:
|
Aluminum alloy
|
Dimension:
|
120×30×38mm
|
Weight:
|
0.11kg
|
(3) Product installation:
1. The lightning protection devices is installed in series between the power lines and the protected device, the output termination is connected with the protected equipment.
2. All wirings must be solid and connected by electric. SPD grounding line: BVR ≥ 2.5mm2.
3. Lightning proof grounding should be consistent with lightning protection regulatory requirements, grounding wire should be as thick and short as possible, resistance should be less than 10Ω.
|